ConnectMQ Edge · IEC 61850 (MMS)

Protection relays and IEDs, live in the cloud

Relay and IED data often sits behind the station HMI, out of reach for the rest of the business. ConnectMQ Edge reads IEC 61850 data over MMS, maps whole bays from an SCL file and uses reports so changes arrive immediately. The values land on your ConnectMQ broker as ISA-95 JSON, ready for dashboards, alerts and the Digital Twin.

  • MMS · port 102
  • SCL import (ICD / CID / SCD)
  • Reports & controls

No card required

Why connect IEC 61850 (MMS) to ConnectMQ

Map a bay from its SCL file

Point Edge at the ICD, CID or SCD file and a tag is created for every ST/MX data object — or let Edge browse the IED online.

Reports instead of polling

Buffered and unbuffered reports deliver changes the moment they happen, instead of waiting for the next poll.

Clean data, even offline

Values reach ConnectMQ as ISA-95 JSON with quality, unit and timestamp, and are buffered on disk while the internet is down.

What it reads and does

  • Protection relays, bay controllers and other IEDs over MMS (port 102)
  • Automatic tags from SCL files (ICD/CID/SCD) or online browsing
  • Buffered and unbuffered report control blocks
  • Controls on [CO] addresses following the IED’s ctlModel, including SBOw
  • Scale and unit conversion, for example W to kW
What arrives in ConnectMQ Cloudconnectmq/site1/substation/bay1/Feeder1/TotW
{ "value": 842.5, "quality": "good", "unit": "kW", "dataType": "Float32", "tag": "TotW", "device": "Feeder1", "channel": "Relays" }

Up and running in three steps

  1. 1

    Install ConnectMQ Edge

    Download Edge from your ConnectMQ account and sign in — the Windows service and desktop app come in one installer.

  2. 2

    Add the IEC 61850 (MMS) channel

    Pick the IEC 61850 (MMS) template, enter the address of your device and the tags you need, and press Save and apply.

  3. 3

    Use the data

    The tags appear in your ConnectMQ broker as ISA-95 topics, ready for dashboards, alerts and the Digital Twin.

Where teams use it

Relay and breaker status at a glance

Status and measurements from every bay in one ConnectMQ dashboard, with alerts on trips and alarms.

Power measurements per feeder

Publish MMXU measurements such as total active power to follow the load of each feeder and site over time.

Substation in the Digital Twin

Bind IED values to the ConnectMQ 3D Digital Twin so operators and engineers see the live state of each bay.

IEC 61850 (MMS): frequently asked questions

How do I connect an IEC 61850 protection relay to MQTT?

Install ConnectMQ Edge on a Windows PC that reaches the IED on port 102, add an IEC 61850 (MMS) channel, enter the IP address and, if you have it, the SCL file, and press Save and apply. Edge publishes the data objects to your ConnectMQ broker over MQTT/TLS as ISA-95 topics with JSON payloads.

Do I need the SCL file of the IED?

No. With an SCL file (ICD, CID or SCD) and "AutoCreateTags": true, Edge creates a tag for every ST/MX data object. Without an SCL file it browses the IED online.

Does ConnectMQ Edge support IEC 61850 reports and controls?

Yes. Edge enables buffered and unbuffered reports that you list under Reports, so changes arrive without polling. Controls on [CO] addresses follow the IED’s ctlModel, including SBOw.

Technical details: step-by-step setup and example configuration

Set it up step by step

  1. 1

    Get the IED IP address (port 102) and, if you have it, the SCL file of the IED. Copy the SCL file into %ProgramData%\ConnectMQ\Edge\scl\.

  2. 2

    In ConnectMQ Edge open Connectors in the left menu, click + Add channel and pick the IEC 61850 (MMS) template.

  3. 3

    The channel is added with sample addresses. In the editor on the right, change the IP address, device settings and tags to match your equipment — the example configuration shows the format. Validate project checks it.

  4. 4

    Press Save and apply. The channel starts right away without restarting the service. Add as many channels as you need, including several of the same type.

  5. 5

    With "SclFile" and "AutoCreateTags": true a tag is created for every data object (ST/MX); without an SCL file the IED is browsed online.

  6. 6

    Add report control blocks under Reports so that changes arrive immediately instead of by polling. Controls ([CO] addresses) follow the IED’s ctlModel, including SBOw.

  7. 7

    Check the result: on Overview the devices show Reading data under Field devices, and problems (wrong address, timeout, rejected login) appear in the Last problem column. The values are in Local OPC UA Server › Live tag values; details are in Windows Service Settings › Logs.

  8. 8

    Open the ConnectMQ portal: the tags appear in the topic tree as <enterprise>/<site>/<area>/<line>/<cell>/<device>/<tag> with a JSON payload (value, quality, unit, timestamp), ready for dashboards, alerts and the Digital Twin.

Example configuration
{
  "Name": "Relays",
  "Driver": "Iec61850",
  "Devices": [{
    "Name": "Feeder1",
    "Isa95": { "Area": "substation", "Line": "bay1" },
    "Settings": {
      "Host": "192.168.10.21",
      "IedName": "REL1",
      "SclFile": "scl/relay1.cid",
      "AutoCreateTags": true,
      "Reports": [{ "Rcb": "LD0/LLN0.BR.brcbST01" }]
    },
    "Tags": [
      { "Name": "TotW", "Address": "LD0/MMXU1.TotW[MX]", "DataType": "Float32", "Scale": 0.001, "Unit": "kW" }
    ]
  }]
}

Good to know

  • Put SCL files in %ProgramData%\ConnectMQ\Edge\scl\ and reference them relative to that folder, as in "SclFile": "scl/relay1.cid".
  • Without report control blocks the values are polled; add them under Reports (for example LD0/LLN0.BR.brcbST01) to get changes immediately.
  • Controls on [CO] addresses follow the ctlModel configured in the IED, including select-before-operate with value (SBOw).
  • Use Scale and Unit to convert values, as in the example: TotW in W with "Scale": 0.001 is published in kW.